Healthcare: Clean Rooms, Laboratories, Pharmacies (Production)
Industry: Clean Rooms, Laboratories and Research Facilities
Education: Research Rooms
Workplace: Data Centres
Hygiene: Antibacterially disinfectable, Cleanable by vacuuming, Virucide disinfectable, Wipeable
Design: Aluminium, Laminate, Steel
Climatic Regulation: Ventilation
Corrosion Protection: Interiors
AIR VELOCITY
0.45 m/s
PRESSURE DIFFERENCE OF FILTER
120 Pa
AIR QUANTITY
2,350 m³/h
OVERALL PRESSURE DIFFERENCE
270 Pa
SOUND LEVEL
50 dB (A)
POWER CONSUMPTION
180 W
HEAT EXCHANGER
The installation of an heat exchanger on the intake side of the unit is possible if the air must be conditioned to temperatures needed. The sensitive (free from condensate) cooling capacity that needs to be provided can be - regarding the flow rate - maximal 7 kW in process areas with a 12 / 12 fan filter unit. From a physiological point of view a much smaller capacity of approx. 2 kW should be pursued for common rooms and workplaces. However, heating capacities can be significantly higher.
THE PARTICLE-FREE WAY TO HANDLE AIR.
Fan Filter Units (FFUs) are used in many fields of application in order to reduce the concentration of particles in cleanroom facilities or parts of it. The fan filter units will be supplied ready for plug-in and are suitable for the use in cleanrooms with turbulent air flows or laminar flows up to class 3 according to DIN EN ISO 14644-1. They can be installed in any Lindner Reinraumtechnik cleanroom ceilings.
decentralized unit including motor, fan and filter
multiple variants of controls available
can be combined with a heat exchanger
numerous sizes available
very small footprint