Adopting a dual circuit design, when one circuit fails, it can be switched to the other circuit; It can achieve non-stop gas maintenance without affecting pressure, meeting the requirement of "continuous gas supply under a single fault" stipulated in GB 50751-2013 "Technical Specification for Medical Gas Engineering". And provide the testing report of GB 50751-2012 "Technical Specification for Medical Gas Engineering"
The pipeline adopts a dual circuit design, with one for backup and one for use
Box size
420mm * 450mm * 170mm
Import pressure P1
0.6-0.8MPa; Export pressure P2: 0.35~0.6MPa (adjustable)
High performance pressure reducer, with a convenient structure for maintenance and debugging;
Degreasing seamless stainless steel 304 pipeline
Configure safety valves to ensure product safety and reliability;
Medium
Oxygen; Flow rate ≥ 300L/min;
Static characteristics
P2 pressure increased by 0.06MPa
Optional addition of bypass valve for easy maintenance