OverviewBag filters combining particulate and molecular media to remove solid and gaseous contaminants in a single filter stage. Suitable for upgrading existing HVAC installations to achieve ePM1 efficiencies per ISO 16890 while also providing molecular adsorption performance according to ISO 10121-3.
Key features- 2-in-1 filtration: particulate capture and molecular adsorption in one filter stage
- Removes solid particles and a range of gaseous contaminants and odors
- Available to upgrade existing systems without major modification
- Galvanized steel header/frame
- Vertical pocket configuration (install with pockets upright)
- Variants classified ePM1 60% (F7) and ePM1 85% (F9)
Available variants0160 592x592x534-10 | ePM1 60% | F7 | 592 | 592 | 534 | 3400 m3/h | Initial Δp 140 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
0160 490x592x534-8 | ePM1 60% | F7 | 490 | 592 | 534 | 2800 m3/h | Initial Δp 140 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
0160 287x592x534-5 | ePM1 60% | F7 | 287 | 592 | 534 | 1700 m3/h | Initial Δp 140 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
0185 592x592x534-10 | ePM1 85% | F9 | 592 | 592 | 534 | 3400 m3/h | Initial Δp 200 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
0185 490x592x534-8 | ePM1 85% | F9 | 490 | 592 | 534 | 2800 m3/h | Initial Δp 200 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
0185 287x592x534-5 | ePM1 85% | F9 | 287 | 592 | 534 | 1700 m3/h | Initial Δp 200 Pa | ISO10121 Ozone: HD 85 | NO2: LD 85 | SO2: MD 55 | Toluene: MD 80
Certifications and badges- ISO 16890: ePM1 classification (particle efficiency)
- ISO 10121-3: molecular filter performance classification
- Efficiency guarantee: stable mechanical filtration efficiency without electrostatic charge
- Molecular badge: tested adsorption for common gases and odors
Characteristics / Technical specifications- Application: particle and odor removal in hospitals, offices, airports and other public buildings
- Filter frame: galvanized steel
- Media: glass fibre media combined with activated carbon for molecular adsorption
- Maximum operating temperature: 50 °C
- Maximum relative humidity: 70%
- Max final pressure drop (EN 13053): initial pressure drop + 100 Pa or initial pressure drop x3 (whichever is lower)
- Dimension standard: filter front dimensions according to EN 15805
- Installation options: front and side access housings and frames available
- Maximum airflow: up to 1.25 x nominal flow
- Installation orientation: vertical pockets (upright)