Product descriptionLAUDA Ultracool UC 65 circulation chillers deliver precise temperature control across an extended operating range from -10 to 35 °C with a temperature stability of ±0.5 K. The unit is rated IP54 for outdoor-capable installation. Standard fan control allows operation at ambient temperatures down to -20 °C and reduces noise emissions. The design reduces footprint compared with previous comparable models. An integrated Ethernet interface is standard and the system can be adapted via options such as speed-controlled pumps or flow meters to meet site-specific requirements.
Features- Industrial circulation chiller with optimized energy performance
- Industrial block pump offering high pressure and high flow
- Compatible with non-flammable process fluids (water, water/glycol)
- Remote operation via integrated web server
- Built-in water filter
- Compliant with EcoDesign directive 2009/125/EC energy requirements
- PID temperature control
- Integrated Ethernet interface
- Uses natural refrigerants
Working range- Min. working temperature: -10 °C
- Max. working temperature: 35 °C
- Temperature stability: ±0.5 K
Cooling capacity (selected temperatures)25 °C : 95.5 kW (50 Hz / 60 Hz)
20 °C : 86 kW (50 Hz / 60 Hz)
15 °C : 77.2 kW (50 Hz / 60 Hz)
10 °C : 67.9 kW (50 Hz / 60 Hz)
5 °C : 58.5 kW (50 Hz / 60 Hz)
0 °C : 49.1 kW (50 Hz / 60 Hz)
-5 °C : 41.5 kW (50 Hz / 60 Hz)
-10 °C: 34.7 kW (50 Hz / 60 Hz)
Technical specifications- Working temperature range: -10 … 35 °C
- Ambient temperature range: -20 … 50 °C
- Temperature stability: ±0.5 K
- Max. filling volume: 125 L
- Max. discharge pressure: 5.0 bar (50 Hz), 7.2 bar (60 Hz)
- Max. pump flow pressure: 250 L/min (50 Hz); 300 L/min (60 Hz)
- Nominal pump flow rate: 196 L/min
- Inlet / outlet connection thread (inside): Rp 1 1/2
- Dimensions (W x D x H): 1040 x 1435 x 1890 mm
- Weight: 440 kg
- Noise level: 69.5 dB(A)
- Power supply: 400 V; 3/PE; 50 Hz & 460 V; 3/PE; 60 Hz