Bed head unit designed for hospital wards to integrate medical gas outlets, electrical services and lighting in a compact three‑chamber profile; suitable for bedside clinical use and built to allow flexible equipment configuration.
Key features
Three‑chamber internal separation for strong electricity, weak electricity and gas pipelines to reduce interaction and enhance safety.
Constructed from aluminum alloy with wall thickness ≥ 1.3 / 1.5 mm; profile width 200 mm, height 55 mm.
Accommodates power sockets, bedside lamps, light switches, medical gas terminals and nurse call equipment; configurable per project requirements.
Panel and base use a buckle‑type modular structure for simplified installation and maintenance.
Surface finishes customizable: spraying, anodizing, wood grain and bespoke color patterns.
Designed with electrical separation and options for double/reinforced insulation or SELV components to mitigate electric shock risk in single‑fault conditions.
Integrated 4W LED lighting, 5‑hole sockets and large rocker switches; options to install flush with the panel.
Equipment belt recommended centre height: 1.4 m above finished floor level.
Specification and dimensions
Width: 200 mm
Height: 55 mm
Material: aluminum alloy
Wall thickness: ≥ 1.3 / 1.5 mm
Structure: three‑chamber (separate slots for strong electricity, weak electricity, gas)
Surface treatments: spraying, anodizing, wood grain, customizable color patterns
Mounting: panel and base buckle‑type modular integrated structure
Lighting: 4W LED fixtures (integrated)
Sockets: 5‑hole sockets
Equipment belt center height: 1.4 m above ground
Compliance and testing
Design concept follows HTM2022 guidance for electrical separation and segregation of services.
Complies with GB 50751-2012 (Technical Specification for Medical Gas Engineering).
Meets GB9706.1-2007 (Medical Electrical Equipment — Part 1: General Requirements for Safety).
Salt spray and other corrosion tests available on request; electrical safety reports provided as required.
Designed to provide electrical fire protection and predictable behaviour under single‑fault conditions.
Configurations can be tailored to project specifications: choice and placement of gas terminals, socket types, lighting options and nurse call interfaces.
Surface finish and color patterns can be customized to match ward interior design.
Panel can be supplied flush or with optional protruding elements per installation preference.
Documentation and test reports are provided to support commissioning and clinical safety verification.